Understanding Harmonics & IEEE 519 Standard
What Are VFD Harmonics?
Harmonics are voltage and current waveforms with frequencies that are multiples of the fundamental power frequency (50 or 60 Hz). Variable Frequency Drives (VFDs) generate harmonics due to their non-linear loads created by the rectification process in the drive's input stage.
Common harmonics produced by 6-pulse VFDs include the 5th (250/300 Hz), 7th (350/420 Hz), 11th, and 13th orders. These harmonics can cause various issues in electrical systems:
- Overheating of transformers, motors, and cables
- Nuisance tripping of circuit breakers
- Reduced power factor and efficiency
- Voltage distortion affecting sensitive equipment
- Resonance with power factor correction capacitors
- Interference with communication systems
IEEE 519 Standard
IEEE 519 is a standard that establishes limits for harmonic currents and voltages at the point of common coupling (PCC) between the utility and the customer. The limits are based on:
- The ratio of short-circuit current (ISC) to maximum load current (IL)
- The voltage level at the PCC
- The harmonic order being considered
IEEE 519 limits are more stringent for:
- Systems with lower ISC/IL ratios (weaker systems)
- Higher order harmonics
- Higher voltage levels
Compliance with IEEE 519 is increasingly required by utilities and can help prevent the issues caused by excessive harmonics.
Harmonic Mitigation Techniques
Passive Solutions
- Line Reactors: 3-5% impedance reactors reduce harmonics by 30-35%
- DC Link Chokes: Similar reduction as line reactors but more compact
- Passive Harmonic Filters: Tuned LC filters can reduce THDi to 5-8%
- Multi-Pulse Drives: 12, 18, or 24-pulse configurations eliminate specific harmonics
- Phase-Shifting Transformers: Used with multiple drives to cancel harmonics
Active Solutions
- Active Front End Drives: IGBT rectifiers with near-unity power factor
- Active Harmonic Filters: Inject compensation current to cancel harmonics
- Hybrid Solutions: Combination of passive and active filtering
- PWM Optimization: Adjusting carrier frequency and modulation techniques
VFD Parameter Optimization
- Carrier Frequency: May affect high-frequency noise
- DC Bus Voltage Control: Affects harmonic spectrum
- Soft Starting: Reduces inrush harmonics
- Load Distribution: Spreading loads across phases